Input |
Capacity |
2000VA/1200W |
Voltage Range (220V) |
140~300VAC |
Frequency |
50/60Hz (Auto sensing) |
Phase |
Single phase |
Socket |
With Fuse |
Cold Start |
Press the ON/OFF switch (0%~100% load) |
Output |
Rating Capacity |
2000VA |
Rating Power |
1200W |
Waveform |
Waveform Battery mode (Simulated Sinewave) AC mode (Sinewave) |
Power Factor |
0.6 |
Rating Voltage |
220VAC |
AC Voltage Regulation |
±10% (Battery mode) |
Rear Output Socket |
4 x Universal (Battery backup) |
Output Frequency |
Rating Frequency |
50/60Hz±1Hz |
Line Mode |
Synchronize with the utility |
Environment |
Tempreature |
0˚C~40˚C |
Humidity |
0%~90%RH (Non-condensing) |
Noise Level |
Less than 45dB |
Indicators |
AC Mode |
Green lighting |
Battery Mode |
Yellow flashing |
Fault |
Red lighting |
Physical |
Dimensions (WxDxH) (mm) |
390 x 125 x 225 |
Net Weight (kg) |
13.4±0.3 |
Transfer Time |
Typical 2~6ms (Max 10ms) |
Communication Interface |
USB/RJ11 (Optional) |
Battery & Runtime |
Rating Voltage |
12V/9AH x 2 |
Recharge Time |
6-8 hrs recover to 90% capacity |
Change Current |
About 1A at Normal mode |
Short Circuit Protection |
Line Mode |
Fuse & firmware protection |
Battery Mode |
Firmware protection |
Overload Protection |
Line Mode |
Load<110%±5% go to fault mode after 5 mins |
Load<120%±5% go to fault mode immediately |
Battery Mode |
Load<110%±5% shut down after 5 secs |
Load<120%±5% shut down immediately |
Protection |
Full Protection |
Overload, discharge & overcharge protection |
Alarm |
Battery Mode |
Sounding every 10 secs |
Low Battery |
Sounding every sec |
Overload |
Sounding every 0.5 sec |
Fault |
Continuously sounding |
Management |
Compatible with OS |
Supports Windows® 2000/2003/XP/Vista/2008/7/8.1/10 |